SD card read/write error
Olası Nedenler
- SD card file system error; card failing
Çözüm
- Format SD card; replace SD card
Recipe file not found
Olası Nedenler
- Recipe CSV file missing from SD card or internal memory
Çözüm
- Re-create recipe file; check file name and path in NB-Designer
Alarm log full
Olası Nedenler
- Alarm buffer capacity reached; old alarms not archived
Çözüm
- Archive and clear alarm log; increase buffer size; check alarm frequency
Touch panel calibration error
Olası Nedenler
- Calibration data lost; digitizer fault
Çözüm
- Run calibration via system menu (hold reset on power-up for NB); replace panel if digitizer failed
Font file missing
Olası Nedenler
- Font not included in project transfer
Çözüm
- Re-transfer including all resources; use standard built-in fonts
Macro runtime error
Olası Nedenler
- Syntax error or runtime exception in NB macro
Çözüm
- Debug macro in NB-Designer; add error handling
Memory full
Olası Nedenler
- Internal flash nearly full with logs/data
Çözüm
- Delete old data; move logging to SD card; reduce log interval
Backlight failure warning
Olası Nedenler
- Backlight near end of life (after ~50,000 hours)
Çözüm
- Replace HMI unit; schedule preventive replacement
FTP upload failure
Olası Nedenler
- FTP server not reachable; wrong credentials; network error
Çözüm
- Check FTP server settings; verify network; confirm username/password
EtherNet/IP communication error (NA series)
Olası Nedenler
- EtherNet/IP scanner connection to PLC lost; tag name mismatch
Çözüm
- Check EtherNet/IP connection settings; verify tag names in Sysmac Studio
OPC UA client error (NA series)
Olası Nedenler
- OPC UA server not running on NJ/NX; certificate not accepted
Çözüm
- Enable OPC UA server on NJ/NX; exchange and trust certificates
USB device error
Olası Nedenler
- Unsupported USB device connected
Çözüm
- Use only supported USB drives (FAT32, ≤32 GB); check USB device compatibility
Printer error
Olası Nedenler
- Printer driver not matching; printer offline
Çözüm
- Install correct driver; check printer connection and power
Time sync error
Olası Nedenler
- NTP server unreachable; wrong server address
Çözüm
- Verify NTP server IP; check network route
Remote desktop connection error
Olası Nedenler
- NA panel VNC not enabled; port blocked
Çözüm
- Enable remote desktop in NA system settings; open TCP port 5900
EtherCAT slave cihaza erişilemiyor
Olası Nedenler
- EtherCAT kablo kopuk
- Slave güç kaybetti
- Slave arızalı
Çözüm
- EtherCAT topolojisini Sysmac Studio'da kontrol edin
- Slave güç kaynağını kontrol edin
- Slave'i değiştirin
EtherCAT slave cihaza erişilemiyor
Olası Nedenler
- EtherCAT kablo kopuk
- Slave güç kaybetti
- Slave arızalı
Çözüm
- EtherCAT topolojisini Sysmac Studio'da kontrol edin
- Slave güç kaynağını kontrol edin
- Slave'i değiştirin
FALS komutu çalıştırıldı - kullanıcı tanımlı hata
Olası Nedenler
- Program içinde kritik durum algılandı
- Güvenlik sınırı aşıldı
Çözüm
- FALS kodu ve mesajını okuyun
- Tetikleyen koşulları araştırın
- Güvenli duruma getirip resetleyin
FALS komutu çalıştırıldı - kullanıcı tanımlı hata
Olası Nedenler
- Program içinde kritik durum algılandı
- Güvenlik sınırı aşıldı
Çözüm
- FALS kodu ve mesajını okuyun
- Tetikleyen koşulları araştırın
- Güvenli duruma getirip resetleyin
I/O konfigürasyon doğrulama hatası
Olası Nedenler
- Takılan modül konfigürasyonla uyumsuz
- Modül arızalı
- Ünite numarası çakışıyor
Çözüm
- I/O tablosunu yeniden oluşturun
- Modül uyumluluğunu kontrol edin
- Ünite numaralarını düzeltin