OMRON Hata Kodları

209 kayıt
E04 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Overcurrent during stop

Olası Nedenler
  • Output short circuit; motor wiring fault
Çözüm
  • Inspect U/V/W cables; test motor insulation; check for shorts
E05 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Overload (electronic thermal)

Olası Nedenler
  • Motor current exceeds OL setting; duty cycle too heavy
Çözüm
  • Reduce load; adjust motor rated current (b012); check b013 (thermal class)
E06 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Braking resistor overload

Olası Nedenler
  • Brake resistor duty cycle exceeded; resistor too small
Çözüm
  • Increase resistor wattage; reduce braking frequency; increase deceleration time
E07 OMRON PLC (CP1L / CP2E / NX / NJ Series)

DC bus overvoltage

Olası Nedenler
  • Deceleration too fast; supply voltage too high; no brake resistor
Çözüm
  • Increase deceleration time; check supply voltage; add/enable brake resistor
E08 OMRON PLC (CP1L / CP2E / NX / NJ Series)

EEPROM write error

Olası Nedenler
  • Power cut during parameter save
Çözüm
  • Cycle power; if persistent, replace drive control board
E09 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Under-voltage (UV)

Olası Nedenler
  • Supply voltage drop; phase loss; input fuse blown
Çözüm
  • Check 3-phase supply; replace fuse; add line reactor
E12 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Drive overtemperature

Olası Nedenler
  • Fan failed; ambient too high; filter blocked
Çözüm
  • Clean filter; check fan operation; reduce load
E13 OMRON PLC (CP1L / CP2E / NX / NJ Series)

CPU error

Olası Nedenler
  • Internal firmware error
Çözüm
  • Cycle power; update firmware; replace drive if persistent
E14 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Ground fault

Olası Nedenler
  • Motor or cable leakage current too high
Çözüm
  • Test motor with megger; check cable for damage; add output reactor
E15 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Output phase loss

Olası Nedenler
  • One motor phase disconnected
Çözüm
  • Check U/V/W motor cable; test motor winding resistance
E21 OMRON PLC (CP1L / CP2E / NX / NJ Series)

RS485 Modbus communication error

Olası Nedenler
  • Communication cable fault; wrong address or baud rate; timeout
Çözüm
  • Check RS485 wiring; verify C071 (baud rate) and C072 (address); check timeout C076
E35 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Thermistor fault (motor PTC)

Olası Nedenler
  • PTC sensor open circuit or short; wrong PTC type
Çözüm
  • Check PTC wiring at C085 terminal; verify thermistor type setting; replace PTC if failed
E40 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Keypad disconnected fault

Olası Nedenler
  • Remote keypad cable disconnected during operation when set as control source
Çözüm
  • Check keypad cable; change control source to terminals (C001) if keypad not used
E41 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Operator disconnect fault

Olası Nedenler
  • Same as E40 but for operator panel
Çözüm
  • Reconnect operator; change to terminal control mode
Err OMRON PLC (CP1L / CP2E / NX / NJ Series)

Parameter setting error

Olası Nedenler
  • Parameter value out of valid range
Çözüm
  • Check parameter against manual; restore defaults with b084=00 then re-enter
Err 00.2 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Regenerative resistor overtemperature

Olası Nedenler
  • External resistor thermal switch tripped; resistor undersized
Çözüm
  • Allow cooling; check resistor thermal switch wiring; replace with larger resistor
Err 10.0 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Parameter checksum error

Olası Nedenler
  • EEPROM parameter data corrupted; power lost during write
Çözüm
  • Restore factory defaults (Fn005); re-enter parameters; replace servo if persistent
Err 16.0 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Overcurrent fault

Olası Nedenler
  • Motor winding short; cable fault; aggressive acceleration; drive undersized
Çözüm
  • Megger test motor; check cables; extend acceleration ramp; check current limit
Err 18.0 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Regenerative energy excess

Olası Nedenler
  • Deceleration too fast; brake resistor missing or too small
Çözüm
  • Connect appropriately sized regenerative resistor; increase deceleration time
Err 21.0 OMRON PLC (CP1L / CP2E / NX / NJ Series)

Encoder communication fault (serial absolute encoder)

Olası Nedenler
  • Encoder cable broken; connector unseated; encoder internal failure
Çözüm
  • Check encoder cable (shielded); check connector; replace encoder unit