Siemens A07483

Brand: SiemensModel: SINAMICS G120 CU250S2Error code: A07483

What the Fault Means

Alarm: EPOS: Travel to fixed stop clamping torque not reached

Likely causes

  • The fixed stop in the traversing block was reached without the clamping torque/clamping force having been achieved.

Solution and Safe First Checks

  1. check the maximum torque-generating current (r1533).
  2. check the torque limits (p1520, p1521).
  3. check the power limits (p1530, p1531).
  4. check the BICO interconnections of the torque limits (p1522, p1523, p1528, p1529).

Safety: do not work inside the panel without isolating the power; if unsure, consult a qualified technician.