Siemens F01653

Brand: SiemensModel: SINAMICS G120 CU250S2Error code: F01653

What the Fault Means

Fault: SI P1 (CU): PROFIBUS/PROFINET configuration error

Likely causes

  • There is a PROFIBUS/PROFINET configuration error for using Safety Integrated monitoring functions with a higherlevel control
  • Note: For safety functions that have been enabled, this fault results in a STOP A that cannot be acknowledged
  • Fault value (r0949, interpret decimal): 200: A safety slot for receive data from the control has not been configured
  • 210, 220: The configured safety slot for the receive data from the control has an unknown format

Solution and Safe First Checks

  1. check and, if necessary, correct the PROFIBUS/PROFINET configuration of the safety slot on the master side.
  2. upgrade the Control Unit software.
  3. remove the PROFIsafe configuring in the higher-level F control or enable PROFIsafe in the drive.
  4. configure the PROFIsafe telegram matching the parameterization in the F-PLC.
  5. PROFIsafe telegram 900 must be configured.
  6. PROFIsafe telegram 30 must be configured.

Safety: do not work inside the panel without isolating the power; if unsure, consult a qualified technician.

Related Siemens error codes

Source: the Zeror.ai industrial fault database and Siemens technical documentation. This page is for information; on critical systems follow the manufacturer's manual and authorised service.