Zeror.ai Error Codes Siemens F01681

Siemens F01681

Brand: SiemensModel: SINAMICS G120 CU250S2Error code: F01681

What the Fault Means

Fault: SI Motion P1 (CU): Incorrect parameter value

Likely causes

  • The parameter cannot be parameterized with this value
  • Note: This fault does not result in a safety stop response
  • Fault value (r0949, interpret decimal): yyyyxxxx dec: yyyy = supplementary information, xxxx = parameter yyyy = 0: No information available
  • xxxx = 9501: It is not permissible to enable the function "n < nx hysteresis and filtering" (p9501.16) in conjunction with the function "Extended functions without selection" (p9601.5)

Solution and Safe First Checks

  1. Correct the parameter value
  2. If xxxx = 9547: With hysteresis/filtering enabled (p9501.16 = 1), the following applies: Set parameters p9546/p9346 and p9547/p9347 acc
  3. to the following rule: p9546 >= 2 x p9547; p9346 >= 2 x p9347 If xxxx = 9522 and 9585: Correct the parameter value.

Safety: do not work inside the panel without isolating the power; if unsure, consult a qualified technician.

Related Siemens error codes

Source: the Zeror.ai industrial fault database and Siemens technical documentation. This page is for information; on critical systems follow the manufacturer's manual and authorised service.