Zeror.ai Error Codes Siemens F35885

Siemens F35885

Brand: SiemensModel: SINAMICS G120 CU250S2Error code: F35885

What the Fault Means

Fault: TM DRIVE-CLiQ (CU): Cyclic data transfer error

Likely causes

  • A DRIVE-CLiQ communication error has occurred from the Terminal Module involved (TM) to the Control Unit
  • The nodes do not send and receive in synchronism
  • Fault cause: 26 (= 1A hex): Sign-of-life bit in the receive telegram not set and the receive telegram is too early
  • 33 (= 21 hex): The cyclic telegram has not been received

Solution and Safe First Checks

  1. check the power supply voltage of the component involved.
  2. carry out a POWER ON.
  3. replace the component involved.

Safety: do not work inside the panel without isolating the power; if unsure, consult a qualified technician.

Related Siemens error codes

Source: the Zeror.ai industrial fault database and Siemens technical documentation. This page is for information; on critical systems follow the manufacturer's manual and authorised service.

Siemens F35885 · Zeror.ai