Siemens A07892

Marca: SiemensModelo: SINAMICS G120 CU250S2Código de error: A07892

Qué Significa el Fallo

Alarm: Drive: Load monitoring pump/fan no load condition

Causas probables

  • The load monitoring is configured for a pump or fan (p2193 = 4, 5)
  • The monitoring function detects when the pump/fan is operating under no load conditions
  • The pump is running in the dry state (no medium to be pumped) – or the fan has a broken belt
  • It is possible that the detection torque threshold is too low (p2191)

Solución y Primeras Comprobaciones Seguras

  1. for a pump, check the medium being pumped, and if required, provide the medium.
  2. for a fan, check the belt, and if required, replace.
  3. if necessary, increase the detection torque threshold (p2191).

Seguridad: no trabajes dentro del cuadro sin cortar la energía; si tienes dudas, consulta a un técnico cualificado.