Siemens A07926

Marca: SiemensModelo: SINAMICS G120 CU250S2Código de error: A07926

Qué Significa el Fallo

Alarm: Drive: Envelope curve parameter invalid

Causas probables

  • Invalid parameter values were entered for the envelope characteristic of the load monitoring
  • The following rules apply for the speed thresholds: p2182 < p2183 < p2184 The following rules apply for the torque thresholds: p2185 > p2186 p2187 > p2188 p2189 > p2190 Load monitoring configuration and response must match
  • It is not permissible that the individual load torque monitoring areas overlap
  • Alarm value (r2124, interpret decimal): Number of the parameter with the invalid value

Solución y Primeras Comprobaciones Seguras

  1. set the parameters for the load monitoring according to the applicable rules.
  2. if necessary, de-activate the load monitoring (p2181 = 0, p2193 = 0).

Seguridad: no trabajes dentro del cuadro sin cortar la energía; si tienes dudas, consulta a un técnico cualificado.

Códigos de error Siemens relacionados

Fuente: la base de fallos industriales de Zeror.ai y la documentación técnica de Siemens. Esta página es informativa; en sistemas críticos sigue el manual del fabricante y el servicio autorizado.