Siemens F07800

Marca: SiemensModelo: SINAMICS G120 CU250S2Código de error: F07800

Qué Significa el Fallo

Fault: Drive: No power unit present

Causas probables

  • The power unit parameters cannot be read or no parameters are stored in the power unit
  • Note: This fault also occurs if an incorrect topology was selected in the commissioning software and this parameterization is then downloaded to the Control Unit
  • See also: r0200 (Power unit code number actual)

Solución y Primeras Comprobaciones Seguras

  1. carry out a POWER ON (switch-off/switch-on) for all components.
  2. check the power unit and replace if necessary.
  3. check the Control Unit, and if required replace it.
  4. after correcting the topology, the parameters must be again downloaded using the commissioning software.

Seguridad: no trabajes dentro del cuadro sin cortar la energía; si tienes dudas, consulta a un técnico cualificado.