Siemens F07982

Marca: SiemensModelo: SINAMICS G120 CU250S2Código de error: F07982

Qué Significa el Fallo

Fault: Drive: Rotating measurement encoder test

Causas probables

  • A fault has occurred during the encoder test
  • Fault value (r0949, interpret decimal): 1: The speed did not reach a steady-state condition
  • 2: The speed setpoint was not able to be approached as the minimum limiting is active
  • 3: The speed setpoint was not able to be approached as the suppression (skip) bandwidth is active

Solución y Primeras Comprobaciones Seguras

  1. check the motor parameters.
  2. carry out a motor data identification routine (p1900 = 2).
  3. possibly reduce the dynamic factor (p1967).
  4. adapt the speed setpoint (p1965) or adapt the minimum limit (p1080).
  5. adapt the speed setpoint (p1965) or suppression (skip) bandwidths (p1091 ... p1094, p1101).
  6. adapt the speed setpoint (p1965) or maximum limit (p1082, p1083 and p1086).

Seguridad: no trabajes dentro del cuadro sin cortar la energía; si tienes dudas, consulta a un técnico cualificado.