Marca: SiemensModelo: SINAMICS G120 CU250S2Código de error: F30650

Qué Significa el Fallo

Fault: SI P2: Acceptance test required

Causas probables

  • at least one checksum-checked piece of data is defective.
  • safety parameters set offline and loaded into the Control Unit.
  • reference checksum incorrectly entered on processor 2 (p9899 not equal to r9898).

Solución y Primeras Comprobaciones Seguras

  1. carry out safety commissioning routine.
  2. again carry out safety commissioning routine.
  3. replace the memory card or Control Unit.
  4. Using STARTER, activate the safety parameters for the drive involved (change settings, copy parameters, activate
  5. check the safety parameters on processor 2 and adapt the reference checksum (p9899).
  6. carry out an acceptance test and generate an acceptance report.

Seguridad: no trabajes dentro del cuadro sin cortar la energía; si tienes dudas, consulta a un técnico cualificado.