Zeror.ai Hata Kodları Siemens A01487

Siemens A01487

Marka: SiemensModel: SINAMICS G120 CU250S2Hata kodu: A01487

Hatanın Anlamı

Alarm: Topology: Option slot component not inserted

Olası nedenler

  • The topology comparison has detected an option slot component missing in the actual topology with respect to the target topology
  • Alarm value (r2124, interpret hexadecimal): ddccbbaa hex: dd = connection number (%4) cc = component number (%3) bb = component class (% 2) aa = component number of the component that has not been inserted (% 1) Note: The component is described in dd, cc and bb, where the component has not been inserted
  • Component class and connection number are described in F01375.

Çözüm ve Güvenli İlk Kontroller

  1. insert the components involved at the right connection (correct the actual topology).
  2. adapt the project/parameterization in the commissioning software (correct the target topology).
  3. check the 24 V supply voltage.
  4. check DRIVE-CLiQ cables for interruption and contact problems.
  5. check that the component is working properly.

Güvenlik: Enerjiyi kesmeden pano içi işlem yapmayın; emin değilseniz yetkili teknisyene danışın.

İlgili Siemens hata kodları

Kaynak: Zeror.ai endüstriyel arıza veritabanı ve Siemens teknik dokümantasyonu. Bu sayfa bilgilendirme amaçlıdır; kritik sistemlerde üretici kılavuzunu ve yetkili servisi esas alın.