Hatanın Anlamı

Fault: Frequency consistency fault

Olası nedenler

  • r0949 = 100: Difference in frequency comparison on P1.
  • r0949 = 101: VFM estimated frequency too high on P1.
  • r0949 = 102: VFM estimated frequency too low on P1.
  • r0949 = 103: Estimated frequency of VFM module was not detected on P1.
  • r0949 = 104: Error in cycle-time on P1.
  • r0949 = 200: Frequency deviation on P2.
  • r0949 = 201: VFM estimated frequency too high on P2.

Çözüm ve Güvenli İlk Kontroller

  1. r0949 = 202: VFM estimated frequency too low on P2.
  2. r0949 = 203: Estimated VFM frequency was not detected on P2.
  3. r0949 = 204: Error in cycle-time on P2.
  4. Increase ramping times p1120 and p1121.
  5. Make sure that drive is not at current limit when starting.
  6. See remedies for F0453.
  7. Check hardware speed estimation circuit.