Marka: SiemensModel: SINAMICS G120 CU250S2Hata kodu: F07984

Hatanın Anlamı

Fault: Drive: Speed controller optimization, moment of inertia

Olası nedenler

  • A fault has occurred while identifying the moment of inertia
  • Fault value (r0949, interpret decimal): 1: The speed did not reach a steady-state condition
  • 2: The speed setpoint was not able to be approached as the minimum limiting is active
  • The speed setpoint was not able to be approached as the suppression (skip) bandwidth is active

Çözüm ve Güvenli İlk Kontroller

  1. check the motor parameters (rating plate data). After the change: Calculate p0340 = 3.
  2. check the moment of inertia (p0341, p0342). After the change: Calculate p0340 = 3.
  3. carry out a motor data identification routine (p1910).
  4. if required, reduce the dynamic factor (p1967 < 25 %).
  5. adapt the speed setpoint (p1965) or adapt the minimum limit (p1080).
  6. adapt the speed setpoint (p1965) or suppression (skip) bandwidths (p1091 ... p1094, p1101).