Inovance E010.1

Бренд: InovanceМодель: MD520 VFDКод ошибки: E010.1

Что означает ошибка

AC drive overload

Вероятные причины

  • Excessive load or locked-rotor
  • High carrier frequency
  • Low bus voltage during high speed running with heavy load
  • Derating at low frequency
  • Output grounding
  • Output phase loss
  • Motor parameter error
  • Flying start not applied when motor started during rotation
  • Encoder direction error
  • AC drive model setting error
  • Inadequate power rating

Решение и первые безопасные проверки

  1. Reduce load; check motor and mechanical conditions
  2. Decrease carrier frequency
  3. Increase input voltage; enable overmodulation function
  4. Avoid heavy load at low speed or select higher power drive
  5. Check for output ground points
  6. Check for output phase loss
  7. Check motor nameplate parameters and perform auto-tuning
  8. Enable flying start (F6-00)
  9. Change encoder A/B phase sequence (F1-30)
  10. Set AC drive model correctly
  11. Replace with higher power drive

Безопасность: не работайте внутри шкафа без снятия напряжения; при сомнениях обратитесь к квалифицированному специалисту.