Бренд: SiemensМодель: SINAMICS G120 CU250S2Код ошибки: A01385

Что означает ошибка

Alarm: Topology: Controller Extension incorrectly inserted

Вероятные причины

  • The topology comparison has detected a controller extension 32 (CX32) in the actual topology that has been incorrectly inserted with respect to the target topology
  • Alarm value (r2124, interpret hexadecimal): ddccbbaa hex: dd = connection number (%4) cc = component number (%3) bb = component class (% 2) aa = component number of the incorrectly inserted component (% 1) Note: The component is described in dd, cc and bb, where the component involved is incorrectly inserted
  • Component class and connection number are described in F01375
  • The drive system is no longer booted

Решение и первые безопасные проверки

  1. insert the components involved at the right connection (correct the actual topology).
  2. adapt the project/parameterization in the commissioning software (correct the target topology).
  3. automatically remove the topology error (p9904).

Безопасность: не работайте внутри шкафа без снятия напряжения; при сомнениях обратитесь к квалифицированному специалисту.