Siemens F01357

Бренд: SiemensМодель: SINAMICS G120 CU250S2Код ошибки: F01357

Что означает ошибка

Fault: Topology: Two Control Units identified on the DRIVE-CLiQ line

Вероятные причины

  • In the actual topology, 2 Control Units are connected with one another through DRIVE-CLiQ
  • As standard, this is not permitted
  • It is only permitted, if the OA application OALINK is already installed on both Control Units
  • Fault value (r0949, interpret hexadecimal): yyxx hex: yy = connection number of the Control Unit at which the second Control Unit is connected xx = component number of the Control Unit at which the second Control Unit is connected Note: Pulse enable is withdrawn and prevented

Решение и первые безопасные проверки

  1. remove the DRIVE-CLiQ connection, restart the systems, install OALINK on both Control Units and commission.
  2. remove the connection to the second Control Unit and restart.
  3. for the S120M component DRIVE-CLiQ extension, interchange the hybrid cable (IN/OUT).

Безопасность: не работайте внутри шкафа без снятия напряжения; при сомнениях обратитесь к квалифицированному специалисту.

Похожие коды ошибок Siemens

Источник: промышленная база неисправностей Zeror.ai и техническая документация Siemens. Страница носит информационный характер; на критичных системах следуйте руководству производителя и авторизованной службе.

Siemens F01357 · Zeror.ai