Zeror.ai Error Codes Siemens F35896

Siemens F35896

Brand: SiemensModel: SINAMICS G120 CU250S2Error code: F35896

What the Fault Means

Fault: TM DRIVE-CLiQ (CU): Inconsistent component properties

Likely causes

  • The properties of the DRIVE-CLiQ component (Terminal Module), specified by the fault value, have changed in an incompatible fashion with respect to the properties when booted
  • One cause can be, e.g
  • that a DRIVE-CLiQ cable or DRIVE-CLiQ component has been replaced
  • Fault value (r0949, interpret decimal): Component number.

Solution and Safe First Checks

  1. carry out a POWER ON.
  2. when a component is replaced, the same component type and if possible the same firmware version should be
  3. when a cable is replaced, only cables whose length is the same as or as close as possible to the length of the

Safety: do not work inside the panel without isolating the power; if unsure, consult a qualified technician.