Zeror.ai Hata Kodları Siemens A08565

Siemens A08565

Marka: SiemensModel: SINAMICS G120 CU250S2Hata kodu: A08565

Hatanın Anlamı

Alarm: PROFINET: Consistency error affecting adjustable parameters

Olası nedenler

  • A consistency error was detected when activating the configuration (p8925) for the PROFINET interface
  • The currently set configuration has not been activated
  • Alarm value (r2124, interpret decimal): 0: general consistency error 1: error in the IP configuration (IP address, subnet mask or standard gateway) 2: Error in the station names
  • 3: DHCP was not able to be activated, as a cyclic PROFINET connection already exists

Çözüm ve Güvenli İlk Kontroller

  1. check the required interface configuration (p8920 and following), correct if necessary, and activate (p8925).
  2. Reconfigure the station via the "Edit Ethernet node" screen form (e.g. with STARTER commissioning software).

Güvenlik: Enerjiyi kesmeden pano içi işlem yapmayın; emin değilseniz yetkili teknisyene danışın.